How can we help you today?

How is the Start/Stop circuit wired for the ATS48 soft starter?

Issue:
Where do you wire the start run circuit for the ATS48 soft starter?

Product Line:
Altistart 48 ATS48

Environment:
All

Cause:
NA

Resolution:
For 2-wire control , jumper the RUN and STOP terminals and wire a run contact between the 24V and RUN terminals.
2 wire control
For 3-wire control, wire a N/C stop contact between 24V and STOP and wire a N/O start contact between 24V and RUN.
3 wire control

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.