The MGP style breakers are NSX breakers with an attachment device for Powerpact 4 boards.
The Zs values for MGP breakers are the same as the equivalent NSX breaker,
Please see the attached files, for the NSX range with the Cmin factor added.

eg - Zs for NSX 160A with TMD trip unit = 0.15 @ 0.4 s  AND Zs for MGP160 with TMD trip unit = 0.15 @ 0.4s  ( 0.95 factor not applied).

Zs value calculation

Schneider Electric UK

Attachment(s)
Zs Values Compact NSX With Micrologic 2.2.pdf [505.86 KB]
Zs Values Compact NSX With TMD Trip 2023.pdf [48.54 KB]