Can the trip units be set in-between settings?

The NSX thermal magnetic trips can only be set at the incremental settings provided, they cannot be set mid way between points.
For example, the Im shown below can only be set to 1250, 1500, 1750, 2000, 2250 or 2500 Amps. Therefore, it is not possible to set to 2100A .

Setting dials on Micrologic Trip unit

This is true for all the ranges of the Micrologic Trip units

Micrologic range from 2.2 to 7.2

It's worth mentioning when Io is present, Io is for base adjustment, and Ir for fine adjustment, please see below a sample from Micrologic 2.2: