How can we help you today?
Are the dimensions changing if we change from copper to Aluminium or vice versa for Oil Distribution Transformers?
Yes,the dimensions are changing if we change from copper to Aluminium or vice versa. The overall dimensions will be affected in case we change the winding material. Usually for the same electrical characteristics (same power rating, same voltage ratio, same impedance, same loss values) the transformer footprint will be bigger if we change the winding material from copper and aluminium for Oil Distribution Transformers.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.