How can we help you today?
In the Magelis iPC, can I open a Windows program within Runtime?
Issue:
In the Magelis iPC, can I open a Windows program within Runtime?
Resolution:
Yes, you can call a Windows program within the Runtime on a Magelis iPC. The script you need to use is:
Sys.createProcess
Function
Only available on XBTGTW and iPC Series targets. Starts an application program on the target machine.
Format
int Sys.createProcess(String processName, String args);
Parameters
Parameter Description
String processName Enter the complete path and file name of the application program.
Use double slashes between drive and directory names.
e.g. C:\\Winnt\\Notepad.exe
The slash is used to denote special characters, such as tab "\t" and new line "\n".
The extra backslash is required to override the special character designation.
String args Enter an argument here when required by the program. Enter an empty string ("")
when there is no argument.
Return Value
Returns 0 when the process ends abnormally. Otherwise, returns the value of the handle. This
handle number is required to terminate a process.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.