How can we help you today?

How do I use the ATV71 keypad to operate my motor?

Issue:
Using the ATV71 keypad to operate a motor.

Product Line:
ATV71

Environment:
All models and serial numbers

Cause:
None

Resolution:
In the ATV71: a  function key will need to be assigned to toggle between Terminal (T) and Keypad (K).
1.  From the MAIN MENU scroll to ACCESS LEVEL, press enter
2.  Scroll down to "Expert", press enter
3.  Press ESC back to the MAIN MENU
4.  Enter on DRIVE MENU
5.  Scroll down to menu 1.6 COMMAND, press enter
6.  Scroll down to "F4 Key assignment", press enter
7.  Scroll down to "T/K", press enter
, ATV71

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.