How can we help you today?

Why the bluetooth interface TCSWAAC13FB does not restart after a power cut when is connected to the PLC TM221

As described in the Hardware Guide of SoMachine Basic, the PLC TM221xx RJ-45 connector with RS485 has some pins that MUST not be connected: Pins 1,2,3 and 6.
Please do not use 8 wires cables, use the cable reference XBTZ9980 (4 wires cable).

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.