How can we help you today?

Does the ATS01 softstart require external thermal overload protection?

Issue:
Is an external thermal overload protection needed to be installed with an ATS01?

Product Line:
ATS01, Altistart 01

Environment:
All

Cause:
N/A

Resolution:
The ATS01 softstart does not provide motor overload protection.  Separate overload thermal protection should be added to the power circuit.  This typically is done with a motor starter upstream of the ATS01.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.