Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does M580 CPU support the CIP service “send RR data”?
Issue

Why is the M580 returning “service not supported “ message?

Product Line

M580, BMENOC

Resolution

M580 supports "Send RR Data" in a successful response to a Forward Open request.

However when configure the M580 as adapter (local slave) to be scanned by a SCADA or Rockwell PLC, the M580 might return a “not supported service” message to the “send RR data” because it doesn’t support Rockwell tags!!

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings