Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Video: Configuring Current Parameters on Altivar 32 & Altivar 320 Drives
Issue:
How low can I set the amperage settings on the ATV32 and ATV320 drives?

Product Line:
ATV32, ATV320

Environment:
All serial numbers for ATV32 and ATV320

Resolution:
On the ATV32 and ATV320 drives, there are 3 amperage settings (nCr, iTH, and CLI)
nCr (Motor Rated Current) - 0.25 to 1.5 In (1) - According to drive rating and [Standard mot. freq] (bFr)
iTH (Motor Thermal Current) - 0.2 to 1.5 In (1) - According to drive rating
CLI (Current Limitation) - 0 to 1.5 In (1)

*In - Drive rated current


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings