Which cable reference can we use between TM3XTRA1 (TM3 bus extension transmitter module) and TM3XREC1 (extension receiver module)?
The extension receiver module TM3XREC1 can be at maximum distance of 5 meters from the TM3XTRA1.
The Catalog recommend to use the references VDIP1845460xx:
- VDIP184546005 (0.5 m)
- VDIP184546010 (1.0 m)
- VDIP184546020 (2.0 m)
- VDIP184546030 (3.0 m)
- VDIP184546050 (5.0 m)
But as these references do not meet the UL requirements, for US market machine installation needs, it’s advised to use 2 other references:
- 490NTW00002U (2.0 m)
- 490NTW00005U (5.0 m)
which are UL rated.