Is it possible to set the date and time on all Sepam series 10 versions?

Issue

Where can one setup the time and date on the Sepam 10 Series?

Product Line

Sepam 10 Series

Resolution

Only Sepam 10A has the option of time and date stamping as it is the only version that can have time-tagged event recording that is why it is the only version where it is possible to set the date and time. Sepam 10 version B and N do not have this time-tagged recording option thus they do not have a real-time clock.

The date and time setting can be accessed in the parameters menu on the Sepam 10A version.

Menu
The parameters to be set are:

  • Date setting (DATE screen)

Date

  • Time setting (TIME screen)

Time

The date and time setting in the parameters menu is not taken into account when the Sepam date and
time are synchronized via the communication.