Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Could you please specify a tightening torque for 87312 / 87312PR and 87313 / 87313PR terminals connection to copper busbars (VBB)
The tightening torque for bolt connection between 87312/87312PR and 87313/87313PR to the Vertical busbar, is same as the tightening torque for NW/MTZ Masterpact and terminal. It will be written at the back portion of the NW/MTZ masterpact.
See attached image. For 87313 and Vertical busbar generally, the torque value is 16-18 Nm. But, for latest torque values, please refer the back side of the NW/MTZ Masterpact.

Schneider Electric UK

Attachment(s)
Torque.pdf [63.96 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings