How can we help you today?
How to get diagnostic information within M221 for its 2 embedded analog inputs?
The M221 PLCs have 2 embedded analog inputs.
The analog values are managed within the SoMachine/Machine Expert - Basic project through the objects %IW0.0 (analog input channel 0) and %IW0.1 (analog input channel 1).
It doesn’t exist diagnostic object %IWS.x.y for these analog inputs (in comparison to TM3 analog input channels).
For these 2 embedded inputs, the diagnostic information is available through the system word %SW80, with the following content:
- bit [0] Set to 1 if all 2 analog channels are in normal state
- bit [6] Set to 1 if an error is detected on analog input channel 0
- bit [7] Set to 1 if an error is detected on analog input channel 1
All other bits are reserved and read at 0.
Note: The general system object %S119 named “Local I/O error detected” do not manage any Analog Input status.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.