What should I check when I/O scanning exchange between an Advantys STB island and a Premium do not work?

1 - Check the IP addresses of the PLC and the STB module
2 - Try pinging the STB module and the PLC from the PC
If it is working:

3 - Check configuration of the Ethernet card in the Premium configuration:
With PL7 Pro and Unity , click on the Ethernet module and check the following parameters:
, The IO scanning box must be selected
In IP address: The IP address of the STB module has been correctly entered
In Unit ID: Enter the value 255
In RD ref slave: Enter the value 5391
In WD slave ref: Enter the value 0
Note:
On an STB module in Ethernet protocol, images of the NIM I/O are at fixed addresses:
Images of the outputs begin from address 40001 --> enter 0 in WR slave ref
Images of the inputs begin from address 45392 --> enter 5391 in RD slave ref

See example screen shot from Unity.

Main Image


Important information:
UnityPro is now EcoStruxure Control Expert. The program made in UnityPro can be opened in this new platform.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings