How can we help you today?

Are there any restriction to the cabling of BMENOC0301 and BMENOC0311 in a standalone system

When the Ethernet backplane port of BMENOC0301 or BMENOC0311 is enabled, the NOC is directly connected to the CPU. The backplane port is not protected by RSTP, Only ports 2 and 3 are protected. Connecting the NOC and the CPU via an external cable may create an unhandled network loop that may impact network communications. Refers to the User Documentation for more details

When the BMENOC's Ethernet backplane port is enabled, do not make any connections between the NOC and the CPU via an external Ethernet cable.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.