Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to get the detail data between DTM in UP and X80 HART module
The communication bwteen DTM and HART module is HART over ethernet, we can capture the trace by wireshark at the service port of CRA if the HART is configured at the RIO Drop, the CRA service port should be configured mirroring the eth backplane.
Refer to the attachment picture, we can get the HART frame in the CIP data field, we can understand it following the HART command protocol.

Schneider Electric UK

Attachment(s)
Microsoft PowerPoint - [Expert Support webinar - X80 HART Rev3- Jan. 28th.pptx]_2.jpg [90.27 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings