How can we help you today?
How can I check the logic inputs are working on an ATV312 drive?
Issue:
Customer is not sure if the inputs are working. Drive is not running.
Product line:
Altivar 312, ATV312
Environment:
all
Cause:
n/a
Resolution:
Go under the SUP menu to LIA-. Under LIA-, select parameter LIS (not LI5A). This will show the Logic inputs from LI1 to LI6. The dash mark will be high (closed) or Low (open). See the attached page from the programming manual, BBV46385 as reference.
Customer is not sure if the inputs are working. Drive is not running.
Product line:
Altivar 312, ATV312
Environment:
all
Cause:
n/a
Resolution:
Go under the SUP menu to LIA-. Under LIA-, select parameter LIS (not LI5A). This will show the Logic inputs from LI1 to LI6. The dash mark will be high (closed) or Low (open). See the attached page from the programming manual, BBV46385 as reference.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.