What can I use as a smaller alternative to the CA3KN or CA2KN range?
Products with part numbers CA3KN or CA2KN are control relays from the TeSys K range with 4 contacts. Schneider Electric also offers the smaller CA2SK or CA3SK with just 2 contacts.
The K relay has 4 auxiliary contacts in the following configurations:
- 4 N/O & 0 N/C
- 3 N/O & 1 N/C
- 2 N/O & 2 N/C
The part number format for the K relay is CAuKNvwxy, where:
u = 2 (AC coil) or 3 (DC coil)
v = number of N/O contacts
w = number of N/C contacts
The last two characters, xy, indicate the coil voltage e.g. BD = 24V DC, P7 = 230V AC
So for an AC control relay with 3 N/O & 1 N/C contacts and a 230V coil, the part number would be CA2KN31P7.
The SK relay has 2 auxiliary contacts in the following configurations:
- 2 N/O & 0 N/C
- 1 N/O & 1 N/C
The part number format for the SK relay is CAuSKvwxy, where:
u = 2 (AC coil) or 3 (DC coil)
v = number of N/O contacts
w = number of N/C contacts
The last two characters, xy, indicate the coil voltage e.g. BD = 24V DC, P7 = 230V AC
So for a DC control relay with 2 N/O & 0 N/C contacts and a 24V coil, the part number would be CA3SK20BD.
Note: It is possible to add additional contacts to both the K and the SK relays, please follow the link below to the catalogue to see these options
TeSys - Chapter B7- Control relays TeSys SK, K, Deca - cial ref - Digicat | Schneider Electric
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.