How to mount GV2* circuit breaker and LC1* contactor to LAD311 mounting plate?
LAD311 is a mounting plate designed to accept the following devices mounted together:
  • GV2ME/GV2P circuit-breakers,
  • TeSys D range contactors: LC1D09-LC1D38,
The combination block to be used to link the power connectors of the two devices prior to mounting onto LAD311, is part number GV2AF4.

Note: When the above two products are not mounted on the LAD311 plate, the circuit-breaker/motor combination block is part number GV2AF3.

If it is an LC1K range contactor, the combination block to be used between this range and the above circuit-breakers is GV2AF01. However, GV2ME/GV2P + Tesys K contactors combined cannot be mounted on LAD311 plate.