What is accuracy of the Rogowski CT's used in the NW breakers?
The accuracy is not given only for the CT but for the trip unit asociated with the CT : the value announce is 1.5% for Masterpact and micrologic 5.0P, or Micrologic 5.0E for current measuring.
We refer to the standard IEC 61557-12.
We refer to the standard IEC 61557-12.
Released for: Schneider Electric UK






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.