What is accuracy of the Rogowski CT's used in the NW breakers?
The accuracy is not given only for the CT but for the trip unit asociated with the CT : the value announce is 1.5% for Masterpact and Micrologic 5.0P, or Micrologic 5.0E for current measuring.
We refer to the standard IEC 61557-12.