Unity Pro : Use of operation on index in INC or DEC function causes a Build error
Goals and Symptoms
When building an application using operation on index in INC or DEC function the build fails with following error message : error during the ARM assembler phase
Code generation failure
Example: INC(my_array[ind*3+1]);
The problem is in Unity Pro V8.0 to V11.0.
Causes and Fixes:
The workaround consits to program the operation outside the function.
Example :
Ind1 :=ind*3+1 ;INC(my_array[ind1]);
When building an application using operation on index in INC or DEC function the build fails with following error message : error during the ARM assembler phase
Code generation failure
Example: INC(my_array[ind*3+1]);
The problem is in Unity Pro V8.0 to V11.0.
Causes and Fixes:
The workaround consits to program the operation outside the function.
Example :
Ind1 :=ind*3+1 ;INC(my_array[ind1]);