How is the S-Flex wired to use or not use the Smoke Purge feature?
Issue:
Wiring S-Flex for the Smoke Purge feature.
Product Line:
S-Flex
Environment:
S-Flex with Bypass option
Cause:
Wiring to enable or disable smoke purge
Resolution:
All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled. To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10. This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18. When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil. The motor will run with full voltage AC power.
Wiring S-Flex for the Smoke Purge feature.
Product Line:
S-Flex
Environment:
S-Flex with Bypass option
Cause:
Wiring to enable or disable smoke purge
Resolution:
All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled. To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10. This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18. When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil. The motor will run with full voltage AC power.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.