PME 8.x applications take a long time to open

Issue
A customer is seeing an issue where the components ( Vista, Designer, Management Console, etc.) of PME can take a half hour or more to open.

Product Line
Power Monitoring Expert 8.0

Power Monitoring Expert 8.1

Environment
Windows server operating systems

Cause
An executable runs on the PME system named "Feature Validator" which can be seen within the Task Manager screen shot below.  This particular program is intended to quickly validate license information when any of the components of PME are opened and then stops running.

Feature validation service

Resolution
An upgraded PME system (depending on the time of the upgrade) can contain multiple active trial licenses causing the Feature Validator program to make a licensing request, but not receive a response from the licensing services. In this situation, multiple instances of the "FeatureValidator.exe" will populate within the Task Manager. In the previous example where this issue was noticed, manually ending these processes temporarily corrected the issue. If trial licenses and full licenses are both in place, manually uninstall all trial licenses per the process in FA278982.

If licenses display as 'Untrusted' through the Floating License Manager they will need to be returned and reactivated or repaired.  This issue has been resolved with the release of PME 8.2, so the customer can upgrade as well.

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support details

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.