Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
When a customer is using a PRM behind a BMeNOC301 with a M580, the PRM looks like loosing his IP address.

Architecture

architecture1


If a customer is using UnityPro V10 or UnityProV11 to configure a PRM behind a BMeNOC it’s mandatory to transfer the Profibus configuration in the PRM. A menu must be used for that: “transfer data to device”.
In a normal situation, at the end of the transfer, the PRM is able to be operational.


Customer vision of the problem:
If the customer adjusts in the DHCP server of the BMeNOC the subnet mask of the PRM, or the gateway address of the PRM, UnityPro send (in fine), a mismatch configuration to the PRM.
In this exemple above we have modified the subnet mask of the PRM from 255.255.0.0 to 255.255.255.0.

tite25
In the configuration screen of the PRM we observe a Subnet mask equal to 255.255.0.0 as it was expected to be 255.255.255.0.

tetrte3

In this condition, at the end of the transfer data to device, the PRM will detect a mismatch in the IP configuration and the PRM will move back in his faulty IP address. 10.10.MAC5.MAC6

Solution:
A Hotfix will be developed in UnityPro V10 and V11.

Workaround:
Pending the availability of the Hotfix a workaround can be used:
After having modified the IP configuration of the PRM in the DHCP server of the BMeNOC, just disactivate the option “DHCP of this device”. Apply it, then active again the option “DHCP of this device” and apply it. At this step you’ll see that the configuration in the PRM match with the new one in the DHCP server.
Transfer the configuration in the PRM. The PRM will not lose his IP address anymore.

tetetde4

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings