How to wire the built in analog input of the M221 to a Dwyer 626 pressure transmitter?

Issue
How to wire the built in analog input of the M221 to a Dwyer 626 pressure transmitter?

Product Line
SoMachine Basic / EcoStruxure Machine Expert-Basic, Modicon M221 PLC

Environment
Analog Input wiring

Resolution
The Dwyer 626 is a 3-wire connection which will requires it's own power supply.
The - (negative of M221) goes to the common and + (positive of M221) goes the white.  See below for more information:

Dwyer pressure transmitter:
Dwyer Pressure Transmitter pinout diagram
The receiver would be the M221 in this case.

M221 Analog Input +/-10V


For the types of wires required, also see the Modicon M221 Logic Controller User Guide
See Section 3.3 "Wiring Best Practices"
Document Link: https://www.se.com/ww/en/download/document/EIO0000000976/

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.