How do we know the clone operation process to create a SD card image is completed with M241/M251 PLCs ?

This FAQ topic refers to the operation named ‘clone’  which consists in getting the whole content of any M241/M251 PLC ( getting both firmware and project application),  make copying it  into an empty SD card

When starting the clone process (powering ON the PLC with an empty SD card inside) the green LED SD is fast flashing, but it’s flashing very fast.
At the end of the process, the SD LED changes state to stay fixed ON until we remove the SD card. But as the eyes can’t really distinguish the difference in the light emitted by the LED between fast flashing and steady On, we can’t really not see  some difference between the two states  ‘clone in progress’ and ‘clone operation completed’

Then to be sure the process ended correctly, it’s recommended:
- to wait up to really 5 minutes after the PLC is Powered ON
- check afterward, the content of the SD card, by plugging it into some SD card reader, to check the file named SCRIPT.CMD is present in the directory  name /sys/cmd  of the SD card ( this is the last action achieved by the system during the clone procedure)

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.