How can we help you today?
How to get the day of the week by program in M580 application ?
For M580 PLC, the DAY_OF_WEEK EF is not available and the system word %SW49 is giving the Day of the week in UTC Time format. To get it in Local time you can import the attached DFB the output is giving the day of the week in the Local Time (defined by the Project Settings->General->Time (Time Zone))
- 1 = Monday
- 2 = Tuesday
- 3 = Wednesday
- 4 = Thursday
- 5 = Friday
- 6 = Saturday
- 7 = Sunday
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.