How can we help you today?
What is the cable to use to connect the HMIGTO to the Premium PLC on the TER port for Unitelway?
Issue:
What is the cable to use to connect the HMIGTO to the Premium PLC on the TER port for Unitelway?
Product Line:
Magelis HMI (XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, XBTGH)
Resolution:
The cable to use would be the XBTZ9780 in order to connect the HMIGTO/XBTGT/HMIGTU/HMISTU/HMISTO to the TSX Premium series PLC via the TER port to communciate over Uni-Telway protocol.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.