How can we help you today?
What is the impedance of the analog input AI1 on the ATV12 drive?
Issue:
Impedance of the ATV12 Analog input AI1.
Product Line:
All ATV12 drives
Environment:
Analog input 1
Cause:
None
Resolution:
Analog input AI1 can be configured as a voltage input or current [AIIt = 5U, 10U or 0A].
Analog voltage input can be configured 0 to +5 V or 0 to +10 V (maximum voltage 30 V). the impedance: 30 kΩ.
Analog current input x to y mA, has an impedance of 250 Ω.
Impedance of the ATV12 Analog input AI1.
Product Line:
All ATV12 drives
Environment:
Analog input 1
Cause:
None
Resolution:
Analog input AI1 can be configured as a voltage input or current [AIIt = 5U, 10U or 0A].
Analog voltage input can be configured 0 to +5 V or 0 to +10 V (maximum voltage 30 V). the impedance: 30 kΩ.
Analog current input x to y mA, has an impedance of 250 Ω.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.