Trio Q & J Radio Multi-Use Serial Port Wiring

Overview

Both the Trio Q and Trio J radios have a multi-use serial port. Each radio features a 9 pin miniature D-Shell (DE-9) female connector that supports two individual serial port connections.

Typical use case for the J (unlicensed 900Mhz/2.4Ghz) or Q (licensed 150Mhz/450Mhz) radios will be Ethernet communications. Yet for legacy applications, a Modbus Gateway (Modbus TCP to RTU protocol converter), or Modbus Serial Device Server (Modbus RTU in TCP) may be configured on the serial port. A serial port may also be configured as a TUI (Text User Interface) for configuration/diagnostics. The TUI diagnostics is useful on systems suffering from high error rates as it provides a basic high speed interface.

Serial port configuration is accomplished with a web browser and the default IP address of both radios is 192.168.2.15. Details of how to configure each radio’s serial port for your application can be found in the Q or J radio documentation installed with TVew+.

Serial Port A & B (J series Radio)

Data Port A uses pins 2 & 3 with pin 5 as the common ground*
Data Port B uses pins 4 & 6 with pin 5 as the common ground*

Serial port pinout

RS-232 Mode
PinNameInput / Output
1Not Used---
2Port A RxDOutput
3Port A TxDInput
4Port B TxD (Diags)Input
5GND---
6Port B RxD (Diags)Output
7Not Used---
8Not Used---
9RSSI / General Purpose PinOutput



* There is no option for RS-485 connections with the J Series radio.

COM Port 1 & 2  (Q series Radio)

COM 1 uses pins 2,3,7 & 8 with pin 5 as the common ground
COM 2 uses pins 4 & 6 with pin 5 as the common ground

serial port DB9

RS-232 ModeRS-485 Mode
PinNameInput / OutputNameInput / Output
1COM 1 DCDOutputNot Used---
2COM 1 RxDOutputB / Z (Inverting)Input / Output
3COM 1 TxDInputA / Y (Non-Inverting)Input / Output
4COM 2 TxDInputNot Used---
5GND---Not Used---
6COM 2 RxDOutputNot Used---
7COM 1 RTSInputNot Used---
8COM 1 CTSOutputNot Used---
9RSSIOutputRSSIOutput



Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.