Why is my drive not storing parameter changes after a power cycle?
Issue:
Parameter changes made to the drive over a network (ModBus, CANopen, etc) reset to default values after a power cycle.
Product Line:
ATV31, ATV312, ATV12, ATV61, ATV71
Environment:
All part numbers.
Adjusments via network
Cause:
Parameter changes are made to RAM and not to EEPROM
Resolution:
Adjustments made over the network are stored to the operating memory (RAM) in the drive so it will be lost after a power cycle.
To have the settings stored to the EEPROM the customer must set Bit 1 of the CMI (Extended control word; address 8504) to 1.
This bit will reset to 0 after a save had been completed.
NOTE: The EEPROM has a limit to the number of times it can be written. This limit is 1,000,000 writes for the ATV312. The ATV12, ATV61 and ATV71 are limited to 100,000 writes.
Parameter changes made to the drive over a network (ModBus, CANopen, etc) reset to default values after a power cycle.
Product Line:
ATV31, ATV312, ATV12, ATV61, ATV71
Environment:
All part numbers.
Adjusments via network
Cause:
Parameter changes are made to RAM and not to EEPROM
Resolution:
Adjustments made over the network are stored to the operating memory (RAM) in the drive so it will be lost after a power cycle.
To have the settings stored to the EEPROM the customer must set Bit 1 of the CMI (Extended control word; address 8504) to 1.
This bit will reset to 0 after a save had been completed.
NOTE: The EEPROM has a limit to the number of times it can be written. This limit is 1,000,000 writes for the ATV312. The ATV12, ATV61 and ATV71 are limited to 100,000 writes.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.