How can we help you today?
What does the Y mean at the end of the ATS48 part number?
Issue:
N/A
Product Line:
Altistar 48
Environment:
Altistart 48
Cause:
N/A
Resolution:
ATS48 has a control supply and a power supply.
On the Y range, you have a control supply that is 110-220 and the power supply is 208-690V. Y range is dedicated for the US market, with NEC standard soft starter that must be protected against the current unbalance. Y range has three current sensors,. There are only 2 on the Q range (one more OLF on the Y range).
On Q range, the control supply is 220-415V and the power supply is 230-415V.
N/A
Product Line:
Altistar 48
Environment:
Altistart 48
Cause:
N/A
Resolution:
ATS48 has a control supply and a power supply.
On the Y range, you have a control supply that is 110-220 and the power supply is 208-690V. Y range is dedicated for the US market, with NEC standard soft starter that must be protected against the current unbalance. Y range has three current sensors,. There are only 2 on the Q range (one more OLF on the Y range).
On Q range, the control supply is 220-415V and the power supply is 230-415V.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.