Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Where do I find the setting for Celsius or Fahrenheit selection within the AP9631 NMC2 Card

Article available in these languages: French

Issue:
Unable to find location of the setting for Celsius or Fahrenheit selection for AP9631, RPDU2, and NetBotz 250


Product line:
AP9630
AP9631
AP9635
RPDU2
NBRK0250


Environment:
5.x and 6.x firmware


Resolution:
Log into the NMC card and look at the top right side where you will see the following:

Figure 1

To change for the logged in user, click on the "apc" or currently logged in user option and you will see the following:
Figure 2

Select US Customary for Fahrenheit and Metric (default setting) for Celsius.

To change this setting for all users, Go to configuration --> security --> Local Users --> Default settings.
You will see similar settings options and again select US Customary for Fahrenheit or Metric for Celsius.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings