Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to realize the data reset in case of slave power off with XXMIT communication
Question:
How to realize the data reset in case of slave power off with XXMIT communication?

Answer:
Regarding the xxmit communication,  the data remains the last good one in case of communication error. In case of power off of modbus slave, the xxmit would retry the connections based on RETRYLMT pin. Then the STATUS should report 116 which means  “Modbus response message time-out”

For customer's requirement, he has to use this error status (116) to clean the input registers buffer by application logic.

Schneider Electric UK

Attachment(s)
xxmit.png [7.98 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings