How can we help you today?

How to realize the data reset in case of slave power off with XXMIT communication

Question:
How to realize the data reset in case of slave power off with XXMIT communication?

Answer:
Regarding the xxmit communication,  the data remains the last good one in case of communication error. In case of power off of modbus slave, the xxmit would retry the connections based on RETRYLMT pin. Then the STATUS should report 116 which means  “Modbus response message time-out”

For customer's requirement, he has to use this error status (116) to clean the input registers buffer by application logic.

Schneider Electric UK

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.