Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why does Vijeo Designer report Error 2897 when I build the application?

Issue:
Somachine / Vijeo Designer reports Error 2897 when I build the application when I only have one device connected to COM1.

Product Line:
Vijeo Designer (all versions), SoMachine (all versions)

Resolution:
This build error occurs in Vijeo Designer when SoMachine has the "SoMachine_Network_Manager" added under COM1 of Somachine configuration.
Why does Vijeo Designer report Error 2897 when I build the application?
To resolve this issue, delete the SoMachine_Network_Manager under COM1 in Somachine and the Vijeo Designer application will build properly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings