Is it possible to monitor the status of NSX switch over modbus?
Yes it is possible, you will need a low voltage OF (29452) connected to a smartlink modbus (A9XMSB11).
See below example of connection:
Connection guide
Link to user guide, see page 46.
https://www.se.com/uk/en/download/document/DOCA0123EN/