Video: How do you set up the ATV630 process drive so HMI dial is speed reference and the terminals are start stop control?

Article available in these languages:

Issue:
ATV630 set up to work HMI as speed reference and terminals as start stop control.

Product Line:
Altivar ATV630 and ATV930 drives

Environment:
All

Cause:
HMI speed reference and terminal 2 wire control for starting.

Resolution:



Programming Sequence

From the Main Menu:
  1. Scroll down (slide your finger around the wheel clockwise) to Menu 5 Complete Settings and press OK
  2. Then scroll down to Menu 5.5 Command and references, press OK, and verify/modify the following parameters:
  • Ref Freq 1 Config = Ref.Freq-Rmt.Term               (sets the keypad to be your speed control)
  • control mode = Separate                                  (your start/stop command and speed reference are coming from different sources)
  • Command switching = Command channel 1    (tells the drive to look at channel 1 for start/stop)
  • CMD channel 1 = Terminals                            (tells the drive what command channel 1 is)
Note: If your drive is already set to I/O Profile control mode, you won't see Not Separate. You would have to go to Not Separate first, and then you would have the option of Separate.
However, going from I/O Profile to Not Separate would force a factory reset. So if you're already set to I/O Profile, leave it in I/O Profile unless you want to do a factory reset.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.