Does the NSX range of circuit breakers offer Generator protection?
Please see the chart below and the online catalogue. In the catalogue, please refer to page B-53.
The Micrologic 2 G trip units are used for the protection of systems supplied by generators and offer better suited low pick-up solutions. They can be mounted on all Compact NSX100/160/250 circuit breakers. Circuit breakers equipped with Micrologic G trip units protect systems supplied by generators (lower short-circuit currents than with transformers) and distribution systems with long cable lengths (fault currents limited by the impedance of the cable).