The Write_Var instruction requires an Array of INT for the EMIS input. How do I move UINT values to a remote device?

Issue:

The Write_Var instruction requires an Array of INT for the EMIS input. How do I move UINT values to a remote device?

Product Line:

Write_var, M340, Control Expert

Resolution:

You simply need to convert the UINT to INT with the UINT_TO_INT block and move the result to the EMIS array.
If the receiving device does not automatically see the data as UINT you would need to use the INT_TO_UINT block
to see the value correctly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.