Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How can you read the status of local or remote via binary point thru bacnet?
Issue:
Reading the status of local or remote via binary point (BacNet)

Product Line:
Altivar 212

Environment:
All serial numbers for Altivar 212

Cause:
N/A

Resolution:
Under the Binary Value Objects Instance, #4 reads and indicates if the drive is locally controlled or not. It is dependent on several other factors as well.
Please reference the chart below

Binary Value


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings