How can you read the status of local or remote via binary point thru bacnet?

Issue:
Reading the status of local or remote via binary point (BacNet)

Product Line:
Altivar 212

Environment:
All serial numbers for Altivar 212

Cause:
N/A

Resolution:
Under the Binary Value Objects Instance, #4 reads and indicates if the drive is locally controlled or not. It is dependent on several other factors as well.
Please reference the chart below

Binary Value