How can we help you today?

What would cause an INF3 fault on the ATV630 drive after you have updated the MCB firmware from version 1.3 to version 1.5?

Article available in these languages:

Issue:
INF3 fault cause on the ATV630 drive after you have updated the MCB firmware from version 1.3 to version 1.5.

Product Line:
Altivar ATV630

Environment:
All

Cause:
Firmware was updated and now they are getting an INF3 fault.

Resolution:
If the Main control board had been flashed on a different size drive HP and voltage  and you put the MCB on another drive not matching that HP and voltage it will trigger a INF3 fault.

Fix:  Replace the MCB with a brand new MCB. If you need to flash the main control board make sure its flashed on the same HP and voltage as the drive its going to be used on.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.