Why I do not succeed to operate a memory (%M and %MW) transfer from SD card to the M221 controller ?
A script command file named script.cmd, present into the SD card and having the line Download “/usr/mem" make possible a transfer into the M221 PLC of %MW and %M values (see Modicon M221 Logic Controller - Programming Guide, section Memory Management: Backing Up and Restoring Controller Memory).

Nevertheless, there are some conditions to make this process being successfully achieved :
1) The script.cmd file should not include any other transfer command like application transfer command (Download “/usr/app") or firmware download (‘Download "/sys/os") which can be present into a script file automatically generated when doing:
2) The SD card has to be inserted into the M221 controller while it is already powered as the script "Download “/usr/mem” is not executed during the boot up, but read and executed by the firmware only when detecting the event of inserting the SD card.
Note: Those two mandatory conditions have to be kept in mind also for a memory upload operation, managed by the command line Upload “/usr/mem”
Nevertheless, there are some conditions to make this process being successfully achieved :
1) The script.cmd file should not include any other transfer command like application transfer command (Download “/usr/app") or firmware download (‘Download "/sys/os") which can be present into a script file automatically generated when doing:
- a clone operation (using an empty SD card)
- a ‘Backup from Controller’ operation command (commissioning Tab in SoMachine/Machine Expert - Basic)
2) The SD card has to be inserted into the M221 controller while it is already powered as the script "Download “/usr/mem” is not executed during the boot up, but read and executed by the firmware only when detecting the event of inserting the SD card.
Note: Those two mandatory conditions have to be kept in mind also for a memory upload operation, managed by the command line Upload “/usr/mem”
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.