How can we help you today?

How to set Analog Output in I/O expansion board to use 4-20 mA instead of 0-20mA?

Title
Analog Output Scaling Formula and Calculation Method for Zero Scale and Full Scale

Language
English

Issue
Users need to calculate Zero Scale and Full Scale values when configuring analog outputs whose hardware output ranges differ from the receiving device’s expected input range.

Product Line
ION Meters
PM8000 Series
ION9000 Series
ION Setup
I/O expansion board

Environment
Meter configuration using ION Setup
Analog Output scaling

Cause
Analog output scaling settings must be calculated when the meter’s analog hardware output range does not match the receiving device’s signal range.

Resolution
The analog output module uses a linear relationship between the Source input and the hardware output. Scaling requires defining the minimum and maximum hardware output values and computing the corresponding Zero Scale and Full Scale values.


Image

Definitions:
Aa = analog hardware output minimum range value
Af = analog hardware output maximum range value
Ax = analog hardware output minimum value
X = scaled equivalent of Aa

The mathematical relationship between the values is shown by the following equation:

(FullScale – X) / (FullScale – ZeroScale)  =  (Af – Aa) / (Af – Ax)

Example
A meter monitors a 0–120 kW system.
The receiving device requires 4–20 mA.
The meter’s analog output hardware range is 0–20 mA.

Variables:
FullScale = 120
X = 0
Af = 20
Ax = 0
Aa = 4

From the scaling equation, Zero Scale = −30
Full Scale = 120

These values produce a 0–120 kW output represented as a 4–20 mA analog signal.

After connecting to your meter in ION Setup, open setup assistant and navigate to Analog Out and choose which output you want to configure.
You can configure the Source, Zero Scale, Full Scale, and port to use for that Analog Output as below:


Setup Assistant

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center