How is the ATV212 remote HMI language changed?
Issue:
Change language on remote HMI connected to the ATV212.
Product Line:
Altivar 212
Environment:
All models
Cause:
Preferred language is different than current setting
Resolution:
The ATV212 integral display provides code, therefore language is not an issue. However, the remote LCD keypad, VW3A1101, provides descriptive readout. If the language needs to be changed, either power up the VFD with the keypad connected, or connect the keypad to a powered VFD. The HMI will initialize itself. When it reaches the Main Menu, there is selection for Drive Menu and Language. Quickly scroll to Language and select it. A list of available languages will appear for selection.
Change language on remote HMI connected to the ATV212.
Product Line:
Altivar 212
Environment:
All models
Cause:
Preferred language is different than current setting
Resolution:
The ATV212 integral display provides code, therefore language is not an issue. However, the remote LCD keypad, VW3A1101, provides descriptive readout. If the language needs to be changed, either power up the VFD with the keypad connected, or connect the keypad to a powered VFD. The HMI will initialize itself. When it reaches the Main Menu, there is selection for Drive Menu and Language. Quickly scroll to Language and select it. A list of available languages will appear for selection.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.