Could not load Licensing.LicenseManager in PME 8.0 after new install
Issue:
When trying to open the Management Console in PME 8.0 after a new install and this error message pops up
Error Message:
"Could not load file or assembly 'Licensing.licensemanager, Version = 1.0.0.0, Culture=neutral, PublicKeyToken=null' or one of its
Product Line:
PME 8.0
Environment:
Software Install
Cause:
Licensing.LicenseManager.resources.dll and Licensing.LicenseManager.dll were not copied to the following three folders:
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Web\bin
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\ReportDataService\bin
Resolution:
To fix this problem, copy Licensing.LicenseManager.resources.dll and Licensing.LicenseManager.dll from one of the existing folders on the computer where PME is installed. (Search the three folders above to copy both files) and then paste into each of the three folders. Each folder should have both files in them.