How can we help you today?

What is the Maximum Zs earth fault loop impedance value for the TM30D trip unit?

For the NSX TM30D breakers at U=218.5V (This is including the Cmin Factor .95 as per BS7671 amendment 3:2015)
- Zs (5s) = 0.722 ohms
- Zs (0.4s) = 0.55 ohms

You can also find the maximum zs values for our circuit breakers such as ComPacT NSX with TMD trip units using the electrical calculation tool link. When you access the tool, select Display T/I curves and select your circuit breaker. This will show the trip curves as well as the maximum zs values.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center