How can we help you today?

What is the minimum voltage rating for DC Bus fuses on Altivar drives?

Article available in these languages:

Issue:
What is the min voltage rating for DC Bus fuses?

Product line:
ATV71, ATV312, ATV320, ATV930

Environment:
All

Cause:
Power is supplied directly to the Altivar DC bus and fuse protection is recommended.

Resolution:
With Line supply voltage of 230-400Vac, use 690Vdc rated fuses.
With Line supply voltage of 440-480Vac, use 800Vdc rated fuses.
With Line supply voltage of 500-690Vac, use 1000Vdc rated fuses.

Schneider Electric UK

Attachment(s)

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.